NV GEBE apologizes for outages

2042
NV GEBE Power plant / File Photo

 

CAPE BAY – In a press release NV GEBE explained that on February 11, at 11: 07am Diesel Generator set # 20 gave an alarm and a few seconds later the engine received a shutdown command from the UNIC software. The shutdown created a sudden imbalance, where the grid stability was affected, and activated the automatic load shedding in order to stabilize the power in the distribution grid.

This led to a large section of the island being affected. This was not a total black out. The press release went on to explain that the company have had some challenges with the software of the new engine, and have been in contact with engine manufacturer Wärtsilä to see what could be the cause and possible solution to this.

Wärtsilä is looking into this problem presently and according to Wärtsilä, “we have observed that something happens to the parameter engine speed reference during a disturbance. This could be why the engine loses load. To understand the reason, there’s the need for a UNIC engineer at site cooperating with Wärtsilä technical service.” The technical engineer arrived on the island over the weekend and will be looking into this issue to resolve this. UNIC is a new software used by the engine manufacturer to control the engine.

When the incident took place NV GEBE mechanics were busy servicing an 11 MW engine and resorted to cutting the service short in order to reduce the load shedding. The servicing will take place at a later date.

Diesel Generator set # 20 has a 1-year warranty as per contract in order to ensure that NV GEBE receives the best results from this unit. The issues above are also covered by warranty.

NV GEBE also has a team from Wärtsilä on site assisting with the mechanical maintenance on an overhaul of a smaller unit.

NV GEBE apologized to its customers and the entire community for the inconvenience caused.